Three Phase Pad Mounted Transformer
Ideal for wind, solar, commercial, and utility power distribution projects.
Contact Us

Three Phase Pad Mounted Transformer Up 44kV 10 MVA

Voltori Energy is a professional supplier of pad-mounted transformers, offering units with voltages up to 44kV and ratings up to 10MVA. All products are cUL certified and meet strict quality standards. We specialize in supporting renewable energy projects across Canada and are well-versed in local codes and standards, including ANSI/IEEE, CSA, DOE, and NEMA. Voltori Energy also provides customized transformer solutions to meet the unique needs of each project.

Radial Feed Type:

Radial feed Transformers will have three high voltage bushings (H1, H2, and H3). There is one bushing for each phase to allow for the incoming high voltage cables. On Wye and Grounded Wye connected Transformers, there will also be an H0 bushing.

Standard Design of Radial Feed Type:

NO. NAME NO. NAME
1HV BUSHING12DRAIN VALVE WITH SAMPLER
2BAY-O-NET FUSE13PAD LOCKABLE DOOR HANDLE
3TAP CHANGER14LIFTING LUGS
4DIAL TYPE THERMOMETER15HAND HOLE & SECURITY COVER
5FILLING PLUG16TANK
6PRESSURE VACUUM GAUGE17COOLING RADIATORS
7LIQUID LEVEL GAUGE18JACKING PAD
8PRESSURE RELIEF VALVE19JACKING PROVISIONS
9LV BUSHING20DOOR
10NAME PLATE212 HOLE HORIZ NEMA GRD PAD
11SERIAL NO22METAL LV-HV BARRIER

Technical Datasheet for Three Phase Pad Mounted Transformer, Radial Feed

Capacity (kVA) High Voltage (V) Low Voltage (V) Tap Changer Loss (W) Overall Size (MM) Weight (KG)
No Load On Load Height Width Depth Oil Total
225 34500/19920
24940/14400
13800/7967
13200/7620
12470/7200
and more
480Y-277
208Y-120
120-240
240-480
347-600
and more
±2x2.5%
±1x5%
and more
390 3025 1575 1300 1325 235 1180
300 485 3650 1575 1320 1345 290 1420
500 680 5080 1575 1372 1397 477 2087
750 969 7600 1651 1448 1575 610 2654
1000 1155 10190 1753 1448 1905 742 3084
1500 1647 14550 1778 1524 2134 954 4264
2000 2156 20850 1803 1600 2184 1060 5035
2500 2677 27800 1880 1727 2312 1219 5798
3000 3210 33360 2032 1778 2743 1272 6396
3750 4050 41700 2057 1854 3226 1378 7121

Loop Feed Type:

Loop feed Transformers will have six high voltage bushings (H1A, H2A, H3A, H1B, H2B, and H3B). There are two bushings for each phase. This allows the customer to connect all of their Transformers in a loop configuration. It will also allow the customer to bring two feeds to the Transformer. A four position switch can be used to switch between the A feed and the B feed.

Standard Design of Loop Feed Type:

NO. NAME NO. NAME
1HV BUSHING13PAD LOCKABLE DOOR HANDLE
2BAY-O-NET FUSE14LIFTING LUGS
34-POSITION T-BLADE S/W15HAND HOLE & SECURITY COVER
4DIAL TYPE THERMOMETER16TANK
5FILLING PLUG17COOLING RADIATORS
6PRESSURE VACUUM GAUGE18JACKING PAD
7LIQUID LEVEL GAUGE19JACKING PROVISIONS
8PRESSURE RELIEF VALVE20DOOR
9LV BUSHING21METAL LV-HV BARRIER
10NAME PLATE222 HOLE HORIZ NEMA GRD PAD
11SERIAL NO23TAP CHANGER
12DRAIN VALVE WITH SAMPLER

Technical Datasheet for Three Phase Pad Mounted Transformer, Loop Feed

Capacity (kVA) High Voltage (V) Low Voltage (V) Tap Changer Loss (W) Overall Size (MM) Weight (KG)
No Load On Load Height Width Depth Oil Total
225 34500/19920
24940/14400
13800/7967
13200/7620
12470/7200

and more
480Y-277
208Y-120
120-240
240-480
347-600

and more
±2x2.5%
±1x5%

and more
390 3025 1626 1351 1325 315 1316
300 485 3650 1626 1371 1345 370 1556
500 680 5080 1626 1423 1397 557 2223
750 969 7600 1702 1449 1575 690 2790
1000 1155 10190 1804 1499 1905 822 3220
1500 1647 14550 1829 1575 2134 1034 4400
2000 2156 20850 1854 1651 2184 1140 5171
2500 2677 27800 2000 1727 2312 1299 5930
3000 3210 33360 2083 1829 2743 1352 6532
3750 4050 41700 2108 1905 3226 1458 7257

Request Free Quote